No user-selectable termination is documented on the ECAN-401. Its user manual defines the CAN pins as CAN_H, CAN_L and CAN_G, with no dial switch and no configuration command for termination, and its wiring section instructs you to fit suitable resistors at both ends of the trunk — it does not say the converter supplies one.

That answer matters because the ECAN family is not uniform. The ECAN-E01 series product page explicitly describes enabling a built-in 120 Ω resistor with a dial switch. The ECAN-401 documentation describes no such switch. Assuming the family behaves the same way is how people end up with a bus carrying three terminators.

Because documentation can lag hardware revisions, the article also gives a 60-second measurement you can run on your own unit before wiring it in.

The short answer

Question

Answer

Adjustable termination switch?

Not documented on the ECAN-401

Termination setting in software?

No — AT commands cover baud, ID, mode and filter only

What does the manual say to do?

Fit 120 Ω at both ends of the bus trunk

How to be certain on your unit?

Measure CAN_H to CAN_L with power off

What the manual actually specifies

The ECAN-401 user manual lists sixteen terminals: RS232 on DB9, power on V+ and V−, the RS485/RS422 pins, and three CAN pins — CAN_G, CAN_L and CAN_H. The ECAN-401 product page repeats the same interface table. The hardware description covers the terminal block, the indicators and the dimensions. There is no termination jumper, no DIP switch position, and no note about an internal resistor in the interface table.

The configuration section is equally silent. The command set covers serial parameters (AT+UART), CAN baud rate and frame ID (AT+CAN), conversion mode (AT+MODE) and acceptance filtering (AT+CANLT). Nothing addresses termination, which is consistent with termination being a wiring decision rather than a device setting.

The CAN wiring section then states the standard requirement: use a linear topology, and fit suitable terminal resistors at both ends of the backbone for impedance matching, with 120 Ω named as the value for runs up to 2 km. That sentence is addressed to the installer, not to the converter.

So the intended design is a converter that sits on the bus like any other node, with the two end nodes carrying the 120 Ω resistors.

CAN termination in two lines: a 120 Ω resistor at each physical end of the trunk, matching the cable's characteristic impedance so reflections die instead of echoing. → Read more: What is CAN termination?

How to check your own unit in 60 seconds

Documentation describes the design; a multimeter describes your board. Before you wire anything:

  1. Power the unit down and disconnect it from the bus.
  1. Set a DMM to resistance and measure across CAN_H and CAN_L.
  1. Read the result against this table.

Reading (power off)

What it means

What to do

Open circuit or above 1 kΩ

No termination inside this unit

Fit 120 Ω at the trunk ends

About 120 Ω

One 120 Ω resistor is present in this unit

Do not add another at this node

About 60 Ω

This unit plus one other terminator in parallel

Correct only if these are the two bus ends

About 40 Ω

Three 120 Ω resistors in parallel

Remove one — the bus is over-terminated

A CAN transceiver's input impedance with the device unpowered is in the kilo-ohm range, so a 120 Ω reading is unambiguous: something resistive is across the pair.

Run this test once and record the result on the drawing. It takes less time than debugging a bus that drops frames only at 500 kbps.

How to terminate the bus correctly

CAN is a differential bus and needs its characteristic impedance matched at both physical ends of the trunk, which is why the value is 120 Ω and why the correct end-to-end measurement on a finished bus is about 60 Ω.

  • Exactly two terminators, one at each end of the trunk. Not one, not three.
  • A mid-bus node carries no terminator. If the ECAN-401 sits in the middle of the trunk, it should not terminate; only the two far ends do.
  • Total measured resistance across the bus should be about 60 Ω with all nodes powered down.
  • Keep stubs short. The manual's linear-topology guidance exists because long branches create reflections that no terminator can fix.
  • Bench tests need termination too. Two short jumper wires on a desk still form a transmission line at 1 Mbps; missing terminators show up as CRC errors that vanish when you slow the bit rate.

If your unit measures open, add a 120 Ω resistor across CAN_H and CAN_L at each end of the cable — a 5.08 mm terminal resistor or an inline terminator plug both work.

Three mistakes worth avoiding

Adding a resistor because "CAN needs termination" without measuring. That is how a properly terminated bus ends up at 40 Ω. Measure first; the DMM decides, not the datasheet.

Terminating at the converter because it is convenient. Convenience is not topology. If the converter is mid-trunk, terminating there adds a third resistor and worsens reflections instead of removing them.

Borrowing the ECAN-E01 answer. The E01 series offers a dial switch for its internal 120 Ω resistor. The ECAN-401 manual shows no equivalent. Treat family similarity as a question to verify, not a fact to copy.

FAQ

Can I enable a 120 Ω resistor on the ECAN-401 by software? No. The documented command set covers serial parameters, CAN baud rate, frame ID, conversion mode and filtering. Termination is not addressable in software on this model.

My ECAN-401 reads 120 Ω across CAN_H and CAN_L. Is it faulty? No. That reading means a 120 Ω resistor is fitted in the unit. If this converter sits at one end of the trunk, that is exactly the terminator the bus needs; do not add another at the same node.

The bus works at 125 kbps but throws errors at 500 kbps. Is that termination? It is the first thing to check. Missing or excessive termination produces reflections that scale with bit rate, so a link that is marginal at low speed and fails at high speed points at impedance, stub length or a third terminator.