E96-DTU(400SL30-485) — SX1262 LoRa Spread Spectrum Wireless DTU | RS485 | 433/470MHz | DIN-Rail Industrial Modem
[Model]:E96-DTU(400SL30-485)
[Chip]:Semtech SX1262
[Frequency]:410–441 MHz (default 433 MHz) · 32 channels · 1 MHz spacing
[TX Power]:20 dBm (configurable)
[Range]:3 km (open field, LoRa spread spectrum)
[Interface]:RS485 (3.81mm terminal block)
[Power Supply]:AC 85–265V (110V/220V) | DC 8–28V
[Size]:92 × 67 × 30 mm · DIN-rail mount · 95 ± 5g
[Introduction]:The E96-DTU(400SL30-485) is an industrial-grade wireless data transmission unit (DTU) based on the Semtech SX1262 LoRa chip. Operating at 433/470MHz with military-grade LoRa spread-spectrum modulation, it provides a transparent RS485 serial interface for seamless integration with PLCs, meters, sensors, and SCADA systems. The DIN-rail plastic enclosure, wide voltage input (AC 85–265V or DC 8–28V), and -40℃ to +85℃ operating range make it ideal for demanding industrial environments.

| Model | Frequency | TX Power | Range | Modulation | Recommended Applications |
| MHz | dBm | km | |||
| E96-DTU(400SL30-485) | 410–441 (default 433) | 20 | 3 | LoRa spread spectrum, anti-interference | Small data volume, long-distance industrial telemetry |
| No. | Parameter | Specification | Remark |
| 1 | Dimensions | 92 × 67 × 30 mm | See installation drawing |
| 2 | Weight | 95 g | ±5g tolerance |
| 3 | Operating Temp | -40℃ to +85℃ | Industrial grade |
| 4 | Antenna Impedance | 50Ω | Standard SMA female |
| 5 | Power Supply | AC 85–265V / DC 8–28V | 110V or 220V AC recommended |
| 6 | Interface | RS485 | 3.81mm terminal block |
| 7 | Baud Rate | Default 9600 bps | Configurable: 1200–115200 bps |
| 8 | Address Code | Default 0 | 65536 addresses available |
| Model | Default Freq (MHz) | Freq Range (MHz) | Channel Spacing | Channels / Duplex |
| MHz | MHz | MHz | ||
| E96-DTU(400SL30-485) | 433 | 410–441 | 1 | 32 channels · Half-duplex |
| Model | TX Current (mA) | Standby Current (mA) | ||
| @ 12V DC | @ 24V DC | @ 12V DC | @ 24V DC | |
| E96-DTU(400SL30-485) | 230 mA | 135 mA | 20 mA | 12 mA |

Ideal Applications
Industrial Automation: PLC-to-SCADA wireless link, remote I/O, frequency converter & sensor telemetry over RS485
Utility Metering: Water / gas / electricity meter data collection, AMR/AMI wireless backhaul
Smart Agriculture: Soil sensor, weather station, irrigation controller wireless data uplink
PV & Energy: Solar inverter monitoring, battery management system (BMS) RS485 wireless bridge
Environmental Monitoring: Air quality, temperature/humidity, noise sensor data aggregation
Frequently Asked Questions
Q: What is the actual transmission range of the E96-DTU(400SL30-485)?
A: In an open field with standard 3dBi antennas at 2m height, the E96-DTU achieves approximately 3 km. Range varies with environment: urban/obstructed areas typically yield 0.5–1 km, while elevated antenna placement can extend coverage further. The SX1262 LoRa chip’s spread-spectrum modulation provides strong anti-interference performance in noisy industrial RF environments.
Q: How do I configure the E96-DTU? Does it require software?
A: The E96-DTU is configured via AT commands over the RS485 interface, or using Ebyte’s free Windows configuration tool (RF Setting). Parameters include frequency channel, TX power, baud rate, address code, and working mode. No programming is required — the DTU operates transparently once configured, passing RS485 data wirelessly without any host-side protocol changes.
Q: Can the E96-DTU support multi-point (point-to-multipoint) networks?
A: Yes. The E96-DTU supports point-to-point, point-to-multipoint, and multi-level relay network topologies. Up to 65536 address codes allow large-scale network segmentation. LBT (Listen Before Talk) is supported for compliance with duty-cycle regulations in EU433 environments.
Q: What power supply options are available?
A: The E96-DTU accepts AC 85–265V (110V or 220V mains) or DC 8–28V via the terminal block. This wide voltage range makes it compatible with standard industrial control cabinets, DIN-rail power supplies, and solar/battery-powered field installations.
Q: Is the E96-DTU compatible with Modbus RTU / SCADA systems?
A: Yes. The E96-DTU provides a fully transparent RS485 serial link, meaning Modbus RTU, DNP3, and other RS485-based protocols pass through without modification. Your existing SCADA or PLC software communicates exactly as if the devices were wired, with no gateway or protocol conversion required.