Ebyte JGD121-EM11 EtherCAT to Modbus TCP RTU Gateway Modbus Master Sla – Ebyte Official Store - IoT Module Manufacturer

Ebyte JGD121-EM11 EtherCAT to Modbus TCP RTU Gateway Modbus Master Slave

$76.08

Shipping calculated at checkout.

The Ebyte JGD121-EM11 is an industrial EtherCAT-to-Modbus protocol conversion gateway that exchanges data between an EtherCAT fieldbus and Modbus TCP or Modbus RTU devices, supporting Modbus master, slave and transparent transfer... Read more

Three Protections: The shell adopts three-proof coating, which is Anti-Fungal, Anti-Humidity, and Anti-Salt Spray.

Shipping: Free Air Shipping Over $89.99(China Post only)If the China post cannot deliver, other logistics need to pay extra postage delivery

Ship From: China EBYTE Manufacturer Factory

Bulk Purchase Tips: Please confirm the firmware version of the test sample with the salesperson before purchasing

Order today. Get it and , hoursminutes

SKU: JGD121-EM11 (EtherCAT to Modbus TCP RTU Gateway, DC 8~28V, DIN Rail)

  • JGD121-EM11 (EtherCAT to Modbus TCP RTU Gateway, DC 8~28V, DIN Rail)
Se enviarán después de [19041994]
Sin existencias

Guaranteed Safe Checkout

paypalvisadiscovermaestroamerican express

Ebyteiot provides invoices. Bulk order discounts. 24/7 tech support, Manuals and certifications available. Product Selection Guide Download: IoT Module&Modem Selection Guide.pdf

Every day, EBYTEIOT serves hundreds of clients worldwide, ensuring that we always remain responsive.

1、Free Shipping Terms

1.1、Free shipping only for wireless modules on orders over $89.99.

1.2、Orders containing Modem, fiberglass antennas, magnetic base antennas or power supply modules are not eligible for free shipping (overweight, magnetic or battery-equipped goods).

1.3、Due to the temporary inability of postal channels to ship to Europe and the United States, goods to Europe and the United States will be delivered via Yanwen Express Line. Please be aware that additional shipping costs may apply to orders to more remote areas.

1.4、We offer shipping insurance in partnership with xcottonsp for all orders.
Simply select the shipping insurance option at checkout. Should your order be undeliverable or lost in transit, you will be reimbursed for the full order value. For more information, please visit:
For consumers wishing to file a claim regarding Shipping Protection, Consumers wishing to file a claim regarding shipping protection may contact Xcotton via any of the following methods:
1. Click the "File a claim" option within the confirmation email received after purchase (subject line: "Xcotton Shipping Protection Placed Successfully").
2. Visit this link to file a claim: https://sp.xcottons.com/parcel#/parcel/parcel-login
3. Contact us via email at:  support@xcottons.com.
4. Claims FAQ:https://sp.xcottons.com/#/more/SPDL5
5. Xcotton Terms and Conditions of Use:https://www.xcottons.com/#/terms/SP-delay

2、Total time

Total time = processing time + shipping time (shipping time is business days)

Processing time = the time between placing an order and us shipping it.

Shipping time = the time it takes for your order to be shipped and delivered to you.

Processing time: 7 working days

Shipping time: 7-30 working days by China Post Air Mail.

We offer express delivery via DHL, FedEx, UPS and more. Extra shipping fees apply: https://ebyteiot.com/products/ebyte-dedicated-link-for-paying-postage

Important Reminder: (Shipment may take several months at maximum due to uncontrollable factors including wars, geological disasters, bad weather and customs clearance.)

3、Customs Duties and Taxes (DDU/DAP)

EBYTEIOT shall not be responsible for any customs duties or taxes incurred by your order. All charges arising during or after shipment (including customs duties, taxes, etc.) shall be borne by the customer.

4、Shipment Confirmation & Order Tracking

Once your order has been shipped, you will receive a shipment‑confirmation email containing your tracking number. The tracking number will become active within 24‑48 hours.
Track your shipment at:  https://www.17track.net/en

5、Damaged & Lost Packages

If you receive a damaged order or your package is lost in transit, please contact us immediately via ebyteiot@cdebyte.com, and provide your order number together with photos of the damaged items.

6、Please be advised that we do not deliver to

  • Cuba
  • Islamic Republic of Iran
  • Democratic People's Republic of Korea (North Korea).
  • Sudan
  • Syria
  • Venezuela
  • Yemen
  • Colombia
  • Israel

We apologize for any inconvenience this may cause.


Cancel order

We accept order cancellations before the product ships. If your order is cancelled, you will receive a full refund. If the product has already been shipped, the buyer can initiate a return or refund request within 30 calendar days of receiving the goods.


Returns

We accept product returns. Customers have the right to request a return within 30 days of receipt of the product. To be eligible for a return, your item must be unused and in the same condition you received it. It must also be in its original packaging. To complete your return, we require a receipt or proof of purchase.

If the return is caused by the consumer, the consumer will bear the shipping costs. The exact cost depends on the courier company you choose.

If the product is damaged or unusable due to our fault, such as product or transportation reasons, please contact EBYTE: ebyteiot@cdebyte.com. After communication with our technical staff, we will arrange for a reissue or refund.


Refund

Once your return has been received and inspected, we will send you a delivery notification via email. We will also notify you of approval or rejection of the refund. If you're approved, your refund will be processed and automatically credited to your credit card or original payment method within 15 business days.


Contact

Contact our customer service at ebyteiot@cdebyte.com.

Tel: +086 028 61543675

Return address: Building B5, No. 199, West District Avenue, High Tech West District Chengdu, China.

 

Auto-download documents via Ebyte official website link:

The Ebyte JGD121-EM11 is an industrial EtherCAT-to-Modbus protocol conversion gateway that exchanges data between an EtherCAT fieldbus and Modbus TCP or Modbus RTU devices, supporting Modbus master, slave and transparent transfer modes over two RJ45 EtherCAT ports (IN and OUT), one dedicated Modbus TCP RJ45 port and one 3.81mm terminal RS485 interface, with a bus cycle as fast as 1~4 ms on the EtherCAT side, a 10 ms minimum cycle on Modbus TCP, 2400~6M bps on Modbus RTU, DC 8~28V supply with reverse-polarity protection and galvanic power isolation, and a 55x30x80mm housing on a standard 35mm DIN rail for -40~+85 degC industrial service.

Key Features & Advantages

  • Three Protocol Worlds In One Module: The gateway speaks standard EtherCAT on the fieldbus side and both Modbus TCP and standard Modbus RTU on the serial / Ethernet side, so an EtherCAT master such as a TwinCAT or Beckhoff PLC can read and write registers held by Modbus instruments, inverters and remote I/O without a separate protocol computer or PC-based driver.
  • Modbus Master, Slave And Transparent Transfer: Beyond plain register mapping, the device can act as the Modbus master polling a bus of RTU slaves, as a Modbus slave exposing its EtherCAT process data, or as a transparent bridge, which is what lets the same part serve both new EtherCAT designs and brownfield retrofits where the Modbus device list is fixed and cannot be re-addressed.
  • EtherCAT with IN and OUT Ports: Two 100M RJ45 ports give a true EtherCAT daisy chain, so the gateway sits inline at the end of a drop cable instead of consuming a dedicated master port. The ECAT indicator exposes the real EtherCAT state machine (INIT off, Pre-OP fast flash, Safe-OP slow flash, OP steady) so a commissioning engineer can read the bus state at the panel without a laptop.
  • 1~4 ms Bus Cycle Against a 10 ms Modbus Floor: The EtherCAT side runs as fast as 1~4 ms depending on master configuration and device count, while the Modbus TCP side has a 10 ms minimum cycle and Modbus RTU runs 2400~6M bps with 8 data bits, 1/2 stop bits and None/Odd/Even parity. That asymmetry is the real design constraint, and it is why the mapping must be planned around a stable data snapshot rather than a per-cycle handshake.
  • Industrial Power Input And Protection: DC 8~28V covers the 12V, 24V and 48V control-voltage families found in cabinets, drawing 2~3W, with a red PWR indicator and documented reverse-polarity protection. The RS485 pair is brought out as A / B / G terminals plus a separate PE earth terminal, which is the correct way to bond a shielded bus without circulating ground current through the signal reference.
  • Field-Serviceable By Design: The Reload button performs three documented actions - a short press under 2 seconds reboots, a 5~10 second hold restores factory settings, and holding while powering up enters firmware upgrade mode - and the SYS and ERR lamps signal upgrade progress. Ebyte also publishes a parameter configuration tool and the ESI file so the device can be imported directly into an EtherCAT master configuration.

Core Specifications

Compiled from the JGD121-EM11 official performance parameter, indicator lamp and interface definition tables. Cells marked [to be confirmed] are not published on the product page and must be taken from the JGD121-EM11 user manual before design freeze.

Category Item Specification
Product Type / role EtherCAT gateway - EtherCAT to Modbus conversion
Protocols Supported EtherCAT, Modbus TCP, Modbus RTU
Protocols Modbus roles Modbus master, Modbus slave and transparent transfer
Power Working voltage DC 8~28V (V+ / V- on 3.81mm terminals)
Power Power consumption 2~3W
Power Protection Power isolation with reverse-polarity protection
EtherCAT port Interface RJ45 x 2 - EtherCAT IN and EtherCAT OUT
EtherCAT port Bus cycle / bandwidth Fastest 1~4 ms (depends on master config and device count); 100M
Modbus TCP Interface / cycle / bandwidth RJ45 dedicated port; minimum cycle 10 ms; 10/100Mbps auto-sensing
Modbus RTU Interface / baud rate RS485 on 3.81mm terminal (A / B / G); 2400~6M bps
Modbus RTU Frame format Data bits 8; stop bits 1/2 (default 1); parity None/Odd/Even (default None)
Indicators Lamps provided PWR (red), SYS (blue), ERR (red), ECAT (blue), TCP (green), RTU (green)
Controls Reload button Factory reset: hold 5~10 s powered on. Reboot: press under 2 s. Firmware upgrade: hold while powering up
Environment Operating / storage -40~+85 degC, 5%~95%RH non-condensing / -40~+105 degC, 5%~95%RH non-condensing
Mechanical Dimensions / weight 55 x 30 x 80 mm (L x W x H, excluding terminals); 140 ± 5 g
Mechanical Mounting Standard industrial 35mm DIN rail
Software Published resources User manual, parameter configuration tool, ESI file for master import
Mapping Register map size / object dictionary [to be confirmed - see user manual]
Mapping Max Modbus RTU slaves polled [to be confirmed - see user manual]
Isolation Rated isolation voltage [to be confirmed - isolation is stated, the rated voltage is not]
Certification EMC / safety certificates [to be confirmed - not stated on the product page]
EtherCAT Jitter / distributed clocks [to be confirmed - see user manual]

Product Selection Guide

Notice for Selection: The JGD121-EM11 is a wired industrial Ethernet gateway - it contains no radio, so no ISM band, antenna or RF certification question applies to this model; the checks that matter are protocol-side. First confirm your EtherCAT master can import the published ESI file and that a 1~4 ms bus cycle suits your motion or I/O scan requirements. Second confirm which Modbus role your site needs: this is a single-order-point product (one EtherCAT-to-Modbus gateway, no variants), so if your application requires a different protocol pair (for example PROFINET or a remote I/O node rather than a protocol gateway) it belongs to a different Ebyte product family and should be confirmed before ordering. Third, verify the register mapping and slave count your project needs against the JGD121-EM11 user manual, since the map size is not published on the product page.

Wiring / integration decision How the JGD121-EM11 handles it What you must confirm
EtherCAT daisy chain, gateway inline at the end of the drop EtherCAT IN from the upstream device, EtherCAT OUT to the next node or terminated Master cycle time and device count, since 1~4 ms depends on both
Existing Modbus TCP instrument or HMI on the plant LAN Dedicated Modbus TCP RJ45 port, 10/100Mbps, 10 ms minimum cycle Whether the gateway or the peer is the Modbus TCP client in your scheme
Legacy RS485 sensor or meter bus RS485 A / B / G on 3.81mm terminals, 2400~6M bps, Modbus RTU Slave addresses, parity and stop-bit settings, and the maximum slave count in the manual
Cabinet with 12V, 24V or 48V control voltage DC 8~28V input, 2~3W, reverse-polarity protected, isolated supply 48V nominal systems exceed 28V and are outside the stated range
Need to expose EtherCAT data to an unrelated Modbus TCP SCADA Modbus slave mode publishes the process data as holding registers Register map layout from the manual, and scan rate versus the 10 ms floor

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 1

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 2

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 3

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 4

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 5

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 6

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 7

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 8

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 9

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 10

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 11

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 12

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 13

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 14

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 15

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 16

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 17

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 18

Ebyte JGD121-EM11 EtherCAT Modbus Gateway Detail 19

Industrial Installation & Wiring

1. Mechanical: Clip the 55x30x80mm housing onto a standard 35mm DIN rail. The quoted dimensions exclude the terminals, so allow the terminal depth plus cable bend radius at the front, and keep neighbouring devices clear of the RS485 and power terminal block so a screwdriver can reach it during commissioning.

2. Power: Feed DC 8~28V to the V+ and V- 3.81mm terminals. The supply is isolated and reverse-polarity protected, but it is still correct practice to fuse the branch and to keep the 2~3W load on a rail shared with relays or contactors away from the noisy coil side. The red PWR lamp confirms the internal rail is up.

3. RS485 bus: Connect A to A, B to B and G to the common reference of the trunk, and bond the cable screen at one end to the PE terminal. Run the bus as a single daisy chain rather than star or tapped branches, set 8 data bits with the stop bits and parity the slaves expect (default 1 stop, No parity), and start at a conservative baud rate before raising toward the 2400~6M bps ceiling, because long or poorly terminated RS485 runs fail at high baud long before the transistors reach their limit.

4. Ethernet: EtherCAT IN receives the drop cable from the master or the previous node, EtherCAT OUT continues the chain. The Modbus TCP port is separate and must not be bridged into the EtherCAT segment - the whole point of the third port is that the two networks stay physically isolated and only the gateway moves data between them.

5. Read the lamps before you open a laptop: ECAT steady blue means OP, slow flash Safe-OP, fast flash Pre-OP, off INIT. SYS steady blue means the device has entered OP; a 500ms slow flash means it has not; off means an operating fault. ERR lit is an EtherCAT communication error. On TCP and RTU, a 200ms fast flash means normal traffic, a 1s slow flash means the channel is enabled but idle, and a 3s steady lamp indicates a communication error on that channel.

6. Commissioning and firmware: Use the published parameter configuration tool to set the Modbus role, mapping and serial parameters, and import the published ESI file into the EtherCAT master so the module appears with the correct process-data description. For firmware work, hold Reload while powering up to enter upgrade mode - SYS and ERR flash together slowly in the upgrade wait state and fast at 0.5s during writing. A 5~10 second hold once running restores factory settings, so record your mapping first.

Practical Application Scenarios

1. Bringing Legacy Modbus Meters and Drives onto a New EtherCAT Line

A machine builder retrofitting an EtherCAT-based line usually keeps the installed Modbus instruments: energy meters, soft starters, VFDs and torque controllers that cannot be re-protocolled. The gateway polls those RTU slaves and republishes their values as EtherCAT process data, so the PLC program sees ordinary inputs and outputs instead of a serial driver, and the 1~4 ms bus cycle keeps the motion-side scan unaffected by the slower serial side.

2. Exposing an EtherCAT Cell to Modbus TCP SCADA or an HMI

Plant SCADA, energy dashboards and third-party HMIs are overwhelmingly Modbus TCP. Running the gateway in Modbus slave mode turns the cell process data into holding registers on the dedicated TCP port, so the supervision system reads it without ever touching the EtherCAT network - a clean security and stability boundary as well as a protocol convenience.

3. Substation, Water and Environmental Telemetry Cabinets

Unattended cabinets aggregate RS485 flow, water-quality and weather sensors under Modbus RTU and hand the data upstream over EtherCAT to a controller or edge gateway. The -40~+85 degC rating, 5%~95%RH non-condensing tolerance, isolated DC 8~28V input and PE-bonded bus make the part usable in unheated kiosks, and the per-channel TCP and RTU lamps let a technician confirm which link died without instrumentation.

4. Test Rigs and Batch Equipment with Mixed Vendor Buses

A test bench frequently mixes a TwinCAT or Beckhoff controller with cheap Modbus power supplies, loads and environmental chambers. Transparent transfer mode passes Modbus requests across the EtherCAT side without the master having to model every register, which shortens integration on one-off equipment where the register documentation is thin and the commissioning window is short.

FAQ Section

Q1: What is the practical difference between Modbus master, slave and transparent transfer on this gateway?

Master mode means the gateway itself initiates requests, so it polls your RS485 or Modbus TCP slaves on a schedule and places the answers into EtherCAT process data - use it when the other devices are dumb responders. Slave mode means the gateway exposes its own registers and something else polls it - use it for SCADA or HMI reads. Transparent transfer passes Modbus frames through without the gateway interpreting every register, which is what you want during commissioning or when the peer device has a non-standard map. Pick the mode first, because it determines how you write the PLC or SCADA side.

Q2: The ECAT lamp is flashing slowly - is the device faulty?

No. The ECAT lamp mirrors the EtherCAT slave state machine: off is INIT, fast flash is PRE-OP, slow flash is SAFE-OP and steady is OP. A slow-flash device has been detected by the master but has not been moved to OP, which is usually a master-side condition - the XML / ESI description does not match the firmware, the expected process-data length differs, or the master has not issued the SAFE-OP to OP transition. Check the master state and the ESI file version before suspecting hardware, and cross-read SYS, which is steady blue only in OP.

Q3: Can I put this gateway on a 48V DC control supply?

No. The stated working range is DC 8~28V, which covers 12V and 24V nominal systems with headroom and, with care, 48V logic supplies that are actually sitting near 24V - but a genuine 48V rail exceeds the specified maximum. Use a DC-DC isolating converter to feed the module 24V, or select a product rated for the 48V family. Note also that a 24V rail derived from an unregulated rectifier under charge can ride above 28V, which is the more common way this input gets over-voltaged in the field.

Q4: Why does my Modbus side look slower than the EtherCAT side, and does that matter?

It is expected and it is a design input, not a fault. EtherCAT is a fast, deterministic on-the-fly copy at 1~4 ms, while Modbus TCP carries a 10 ms minimum cycle here and Modbus RTU is bounded by baud rate, slave turnaround and frame length. The gateway therefore samples or refreshes Modbus data at Modbus speed and publishes it to the bus at EtherCAT speed. Size your application around that: use the EtherCAT side for values the control loop consumes, do not build a control loop that waits on a Modbus round trip inside one bus cycle, and if you need faster serial data, raise the baud rate, shorten the trunk or split the slaves across two buses.

SKU

JGD121-EM11 (EtherCAT to Modbus TCP RTU Gateway, DC 8~28V, DIN Rail)

Disclaimer:This product is strictly prohibited for use in military applications and scenarios related to life safety. The user shall be fully liable for any unauthorized use.

domingo,lunes,martes,miércoles,jueves,viernes,sábado
enero,febrero,marzo,abril,mayo,junio,julio,agosto,septiembre,octubre,noviembre,diciembre
No hay suficientes ítems disponibles. Solo quedan [max].
Agregar a favoritosRevisar favoritosRemover favoritos
Bolsa de compras

Tu bolsa de compras está vacía.

Return To Shop

Agregar notas a la ordenEditar notas de la orden
Estimar envío
Agregar un cupón

Estimar envío

Agregar un cupón

Tu código de cupón se aplicará en el checkout

Ebyte JGD121-EM11 EtherCAT to Modbus TCP RTU Gateway Modbus Master Slave

$76.08