Two E34 modems that talk to each other perfectly, and a Solis S6-EH3P(3-12)K-H that ignores them. That combination is more common than it looks, and in most cases it has nothing to do with the radio.

The pair working proves the RF link, the power supply and the addressing between the two modems. What it does not prove is that the link can carry Modbus RTU inside the timing window the inverter expects. A transparent radio bridge is invisible to the protocol only if three things hold: the serial parameters match on both sides, a complete Modbus frame goes out as one packet, and the round trip finishes before the inverter gives up.

Those are exactly the three things a bench test between two modems never exercises. This article walks the settings in an order that finds the fault early.

For reference, the E34 series is sold as the E34-DTU(2G4Dxx) and (2G4Hxx) family — 2.4 GHz, RS232/RS485, air rates from 250 kbps to 2 Mbps. The model you know as E34-DTSU behaves as a transparent RS485 bridge, which is what the inverter sees.

Step 0: prove which side is actually failing

Before changing a single parameter, remove the radio from the path. Run one cable from the meter's RS485 terminals to the inverter's meter port and check whether the inverter reads energy data.

  • It reads. The meter, its address and the inverter's meter settings are correct. The fault is in the radio path — go to Step 1.
  • It still does not read. The radio was never the problem. Fix the meter address, the meter type selection or the A/B wiring first; a perfect radio link cannot repair a wrong address.

This test takes ten minutes and saves hours. Almost every "the modems don't work with the inverter" case that ends in a firmware discussion would have been caught here.

Step 1: match the serial parameters to the inverter, not to each other

This is the most common failure and the easiest to miss. When you commission two modems back to back, any matched baud rate works. With an inverter in the circuit, one specific rate is required.

The Solis S6-EH3P speaks Modbus RTU at 9600 bps, 8 data bits, no parity, 1 stop bit, with slave address 1 — the defaults published for the S6-EH3P register map and repeated in third-party integration notes for the same platform. The DTSU666 meter on the other side also communicates over RS485.

Set both modems to 9600 8N1. If the meter is configured for a different rate than the inverter, the two ends cannot both be satisfied by a transparent bridge — align the meter to the inverter, not the reverse.

Parameter

Set to

Why

Serial baud

9600

Matches the Solis meter port

Data format

8N1

No parity on the S6-EH3P

Air rate

As high as the link tolerates

Lower air rate means longer round trips

Sub-packet threshold

Long enough for a full Modbus frame

Splitting a frame breaks its CRC

Auto-retransmit

Off while commissioning

A duplicate request produces a duplicate reply

Frequency hopping

On

The inverter is a 2.4 GHz noise source

Step 2: stop the link from breaking frames

A Modbus RTU frame is delimited by silence: the receiver treats a gap longer than 3.5 character times as end-of-frame. Transparent radios do not know that. They forward bytes as they arrive, and most of them flush a packet on an idle timeout.

If that timeout is shorter than the time it takes the inverter to send its request, the frame arrives in two pieces. The meter sees a truncated request with a bad CRC, discards it, and stays silent. The inverter reports a timeout. Nothing in either log says "the radio split the frame".

Set the sub-packet threshold on both modems long enough that a complete request goes out in one packet, and long enough that a complete reply comes back in one packet. If the modem exposes a fixed-length packet mode, prefer it over a timeout-based one.

The same mechanism explains a subtler failure. If automatic retransmission is enabled, a request that was received but whose reply was lost can be sent twice. Modbus RTU has no transaction identifier, so the meter answers twice, and the inverter receives a second response it never asked for — which reads as a protocol error, not a retransmission.

Step 3: configure the meter side of the inverter

A Solis hybrid uses an external meter with three CTs to decide how much power to curtail. If the meter is not being read, export control has no input.

Three settings matter on the inverter:

  • Meter address. Solis assigns address 001 to the grid-side meter and 002 to a second meter on a PV inverter, as the S6-EH3P manual shows in its AC-coupled diagram. A DTSU666 left at a different address will not be polled.
  • Meter type. The inverter must be told which meter family it is talking to. A meter of a different family may share the RS485 wiring and still answer nothing the inverter understands.
  • Frame spacing. Solis integration guidance calls for more than 300 ms between query frames. If your commissioning tool polls faster than that, it can mask a working installation or produce timeouts that look like radio faults.

Once the meter reads, enable the export limit or self-use mode so the data is actually used, and check the CT ratio and direction — reversed CTs give negative power and confuse the control loop rather than the link.

Step 4: the physical layer, in the order it fails

  • A and B swapped. RS485 survives many things but not reversed polarity. Swap and retest; it costs nothing.
  • No common reference. The meter, the modem and the inverter should share a signal ground. Long, floating runs pick up the inverter's switching noise.
  • Termination. Two 120 Ω resistors, one at each physical end. A short bench link may work without them; a cable run through a plant may not.
  • Antenna placement. Keep the 2.4 GHz antennas out of the inverter's metal enclosure and away from the DC and AC cables. A link that works on the bench can collapse beside a switching power stage.

Symptom-to-cause table

What you see

Most likely cause

First fix

Inverter shows no meter data, radio link LEDs healthy

Baud or frame format mismatch

Set both modems to 9600 8N1

Meter data appears, then drops out

Frame splitting or air-rate starvation

Lengthen sub-packet threshold, raise air rate

Occasional protocol errors, not clean timeouts

Duplicate replies from auto-retransmit

Disable retransmission

Works with a cable, fails over radio

Latency beyond the inverter's timeout

Raise air rate, shorten packet timeout

Negative or nonsensical power readings

CT direction or ratio

Reverse CTs, verify ratio

Nothing at all, even with a cable

Address, meter type or A/B wiring

Step 0, then address 001

FAQ

Do I need to change anything inside the inverter's firmware? No. The S6-EH3P polls its meter over Modbus RTU at 9600 8N1 with a standard address. A transparent radio bridge that preserves frames and timing is invisible to it. The work is in the modem settings and the meter address, not in firmware.

Why did the two modems work perfectly before the inverter was connected? Because two modems only have to agree with each other. An inverter adds a timing contract — request, response and a maximum gap — that a back-to-back test never exercises. The link was always fine; the frame handling was not tested.

Can I use a lower air rate for better range? You can, but check the round trip. Lower air rate lengthens every frame, and the inverter's meter poll has a deadline. If you need range, raise antenna gain or move the antenna before dropping the air rate below what the poll interval allows.